More refrigerant than specified can also create serious problems.
Possible symptoms
High condensing pressure, increased subcooling, high power consumption, and potential triggering of high pressure protection.
Effect on the condenser
Excess liquid refrigerant may occupy part of the heat exchanger and reduce the effective condensing surface area.
Diagnosis
Charging is confirmed using the manufacturer's data and not just from a single pressure reading.