More refrigerant than specified can also create serious problems.

Possible symptoms

High condensing pressure, increased subcooling, high power consumption, and potential triggering of high pressure protection.

Effect on the condenser

Excess liquid refrigerant may occupy part of the heat exchanger and reduce the effective condensing surface area.

Diagnosis

Charging is confirmed using the manufacturer's data and not just from a single pressure reading.