The high pressure alarm protects the compressor when the pressure on the high side of the refrigerant circuit exceeds the permissible limit.

In heating mode

Low water flow, a clogged exchanger, or an excessively high supply temperature can increase the condensation pressure.

In cooling mode

Restricted airflow to the external exchanger or a fan failure can lead to high pressure.

Other causes

Incorrect refrigerant charge or a problem with the refrigerant circuit valves.

Diagnosis

Actual pressures, temperatures, flow rates, and the condition of the exchangers are checked before any reset is performed.