A burner may ignite normally but remain at low fire or stop before reaching the required load.

Demand signal

Check if the PLC, BMS, or controller is actually sending a command for a higher load.

Servomotor and feedback

The actual air and gas position is compared against the command. If the actuator does not follow, modulation is restricted.

Load limits

Temperature, boiler pressure, draft, or another process limit may be restricting the load without an actual fault.

Gas pressure limitation

If the pressure drops as the load increases, the BMS may not allow further output increase.

Commissioning curve

After an actuator change or adjustment, it must be verified that the modulation curve is correctly parameterized.