Flue Gas Analysis

Flue gas analysis

Typical values per fuel and a calculator from your analyser readings (Siegert formula).

FuelO₂ %CO₂ %CO₂max %COFlue tempλqA max
Natural gas
Check leaks and chimney draught.
2–68,5–10,511,7< 100 ppm120–180 °C (συμπύκνωσης 40–80 °C)1,10–1,40≤ 9 %
LPG
Heavier than air — mind ventilation.
2–610–1213,7< 100 ppm120–180 °C1,10–1,40≤ 9 %
Heating oil / Mazout
Smoke number (Bacharach) ≤ 1, no oil traces.
3–512–13,515,4< 80 ppm160–220 °C1,15–1,30≤ 10 %
Pellets / wood
CO limit ~500 mg/m³ at 13% O₂ (Ecodesign, automatic feed).
6–1010–1420,3≤ 500 mg/m³120–200 °C1,4–2,0≤ 15 %
Excess air λ
1,24
CO₂ (%)
9,5
Flue gas loss qA
6,2 %
Combustion efficiency
93,8 %
Undiluted CO
49 ppm
O₂ (%)
4

Green = within typical range, red = outside. Indicative values — always follow the manufacturer and current legislation (in Greece KYA 189533/2011).