Over time, a sensor may show a slight deviation from the actual value. Some controllers offer a calibration offset feature.
First, verification
Before applying an offset, the reading should be compared against a reliable reference instrument.
Small, constant deviation
This can be corrected with a calibration parameter if the manufacturer allows it.
Large or unstable deviation
This may indicate a faulty sensor, a bad connection, or a wiring problem and should not simply be covered by an offset.
Documentation
Every calibration change must be documented so that it is known for future service.



